What a Three Winding Transformer Actually Is
A three winding transformer is a power transformer built with three electrically independent windings on a single magnetic core. One winding is the primary, connected to the supply voltage; the other two are secondary windings, each delivering a different voltage level. Instead of stepping power down in two separate stages through two transformers, one unit handles the whole conversion. For readers new to the topic, the simplest way to picture it is a single core with three sets of copper conductors, magnetically coupled but electrically isolated, each sized for its own voltage and current.

The third winding is often called the tertiary winding. It may carry real load, such as feeding a 10 kV auxiliary bus from a 35 kV incoming line, or it may serve a technical purpose: providing a path for zero-sequence current, supplying reactive compensation equipment, or reducing harmonic distortion. That dual role is what makes the three winding transformer more interesting than a simple two-winding unit, and it is also where most specification mistakes happen.
Why Use One Unit Instead of Two Transformers
Procurement teams usually compare the three winding transformer against two cascaded two-winding units. The single-unit approach wins on several counts:
- Footprint: one tank or one enclosure instead of two, which matters on congested substation platforms and rooftop or indoor rooms.
- Capital cost: fewer bushings, fewer protection relays, fewer foundations and less cabling.
- Efficiency: losses are incurred once rather than twice across two conversion stages.
- Voltage regulation: the two secondary voltages stay tied to the same primary reference, which simplifies coordination of protection settings.
- Maintenance: one oil system, one cooling circuit, one set of routine tests per cycle.
The trade-off is that the unit is heavier, the fault level on the common core is higher, and a failure affects both secondary systems at once. That is why redundancy planning still matters in critical installations.
Typical Construction, Connections and Cooling
In the distribution range, most units are oil-immersed, with windings immersed in insulating oil and cooled by natural oil circulation, designated ONAN, sometimes upgraded to ONAF with fans for higher capacity. Dry-type designs use cast-resin or resin-encapsulated windings and are preferred where oil is unacceptable: inside buildings, in tunnels, near water treatment areas, or in fire-sensitive process plants. In the Runsheng Transformer Co., Ltd. catalogue, these map to the S11, S13, S20 and S22 oil-immersed families and the SCB10, SCB13, SCB14 and SCB18 dry-type families, with ratings commonly spanning 30–6300 kVA.
The winding arrangement is described by a vector group symbol. Common configurations include YNyn0d11, where the high-voltage winding is star-connected with a neutral brought out, the low-voltage winding is also star-connected with a neutral, and the tertiary is delta-connected to stabilise the zero-sequence path. A delta tertiary is especially useful where unbalanced single-phase loads or third-harmonic currents are expected. The choice of vector group is not cosmetic; it governs neutral availability, earth-fault protection behaviour and paralleling conditions.
Key Parameters to Confirm Before Ordering
An accurate datasheet is the difference between a machine that runs quietly for thirty years and one that trips protection every summer. Confirm each of the following in writing:
- Capacity ratio across the three windings, for example 100/100/50, since the tertiary is rarely rated at full power.
- Voltage ratio and tap range, including whether the tap changer is off-circuit or on-load.
- Impedance voltage for each winding pair, not just the high-to-low value. High-to-tertiary and low-to-tertiary impedances affect short-circuit withstand and voltage dip.
- No-load loss and load loss at reference temperature, with the measurement standard stated.
- Cooling class, temperature rise limits and insulation level for each winding.
- Enclosure or IP rating, cable entry direction and terminal layout for dry-type units.
- Applicable standards and the test programme: routine tests on every unit, plus type tests where the design is new or the project demands them.
Where These Units Earn Their Place
Real installations tend to cluster into a few patterns. Step-down substations on 35 kV and below use a three winding transformer to supply two distribution voltage levels, typically 10 kV and 0.4 kV, from one incoming feeder. Renewable energy projects use them to combine collection voltage and station service supply. Industrial plants with mixed motor and process loads use the tertiary to feed capacitor banks or harmonic filters. Mining and heavy process sites favour robust oil-immersed units with reinforced insulation and dust-resistant cooling. In all these cases the same rule applies: size the unit for the load profile, not for the nameplate habit.
Buying Pitfalls Worth Checking
Price gaps between quotations for the same nominal rating are usually not random. They come from specific differences that buyers can verify:
- A tertiary winding quoted at a very low capacity percentage that cannot actually carry the intended auxiliary load.
- Loss figures stated for no-load only, hiding poor load-loss performance that costs money every operating hour.
- Core grade substituted during production, where a unit sold as low-loss is delivered with conventional laminations.
- Impedance values given for a single winding pair, leaving the tertiary behaviour undefined.
- Inspection documentation promised but not included, making acceptance testing at site impossible to benchmark.
Comparing on total cost of ownership, not on purchase price alone, resolves most of these questions. Loss evaluation over a ten-year horizon often outweighs a small initial discount.
What a Reliable Supplier Should Provide
Documentation is the cheapest insurance in transformer procurement. A serious manufacturer supplies an operation manual, factory inspection report, routine test certificate and a traceable quality record covering the life of the unit. As a transformer manufacturer serving both standard distribution demand and custom projects, Runsheng Transformer Co., Ltd. ships every unit with this documentation package and offers factory-direct pricing on oil-immersed and dry-type designs, including special types such as mining, rectifier and capacity-regulating transformers, together with preassembled and compact substations and high/low-voltage switchgear for complete station packages.
Quick Answers to Common Questions
- Can a tertiary winding be left unloaded? In many designs yes, but the delta tertiary must still be rated for circulating harmonic current; confirm the design intent with the manufacturer.
- Oil-immersed or dry-type? Choose dry-type for indoor, fire-sensitive or oil-restricted sites; oil-immersed for outdoor substations and higher capacities.
- How long is typical delivery? Standard ratings from stock move quickly, while custom vector groups and special impedances need a design and test cycle, so plan early.
For specification support, drawings or a quotation on a three winding transformer, contact the team directly: phone +86 13406394988, e-mail runsheng@7813transformer.com, WhatsApp 008613508930968.





